Error codes
SMA inverter error codes
SMA inverters show a numbered event on the display, in the Sunny Portal or in the SMA Energy app, often with a short message such as "Grid fault". Note the number exactly; the first safe check is whether the house itself has power and the solar breaker in your fuse box is on.
By Scott Charles, Bolido Solar
Updated
Grid faults
The inverter has disconnected because the grid was outside the limits it is allowed to work in. The inverter itself is usually fine.
101–103Grid fault: voltage too high
The grid voltage at your connection went above the limit, so the inverter disconnected. It reconnects once the voltage settles.
- Safe to reset?
- Safe to restart
- When to call an engineer
- If it happens most sunny afternoons, ask your DNO to check the supply voltage first. If they find nothing, we check the cable between the inverter and the fuse box.
202–205Grid fault: grid lost or voltage too low
The inverter cannot see a healthy grid. Causes include a power cut, a tripped solar breaker or a damaged AC cable.
- Safe to reset?
- Check first
- When to call an engineer
- Check the solar breaker and the AC isolator. If both are on and the house has power, call an engineer.
301Grid fault: 10-minute average too high
The average grid voltage over ten minutes went above the permitted level. Common where a lot of solar feeds the same street on a sunny day.
- Safe to reset?
- Safe to restart
- When to call an engineer
- If it repeats daily, contact your DNO first, then us.
401, 404Grid fault: islanding or sudden frequency change
The inverter saw the grid behave as if it had been cut off, or change frequency sharply, and disconnected as a safety measure.
- Safe to reset?
- Safe to restart
- When to call an engineer
- Call us if it happens often on otherwise normal days.
501, 701Grid frequency out of range
The grid frequency went outside the permitted range. A persistent 701 can also mean the inverter country settings do not match the grid.
- Safe to reset?
- Check first
- When to call an engineer
- If 701 stays after a firmware update or settings change, an engineer needs to check the country data set.
Wiring and connection
901Earth connection missing
The inverter cannot find a proper earth (PE) connection.
- Safe to reset?
- Leave it, call an engineer
- When to call an engineer
- Call an engineer. Do not keep restarting it.
1001Live and neutral swapped
Live and neutral are reversed at the inverter AC connection, usually after installation or other electrical work.
- Safe to reset?
- Leave it, call an engineer
- When to call an engineer
- Call an engineer to correct the wiring.
1302Waiting for grid voltage
The inverter cannot see the grid on live or neutral.
- Safe to reset?
- Check first
- When to call an engineer
- Check the solar breaker and AC isolator. If both are on, call an engineer.
Panels and DC side
These relate to the panels and the DC cabling from the roof. Insulation and overvoltage faults need an engineer.
3301–3303Unstable operation
Not enough power from the panels for the inverter to run steadily. Normal at dawn, at dusk and under heavy cloud.
- Safe to reset?
- Safe to restart
- When to call an engineer
- Only a concern if it shows at midday in good light.
3401–3407DC overvoltage
The voltage from the panels is above what the inverter can take, which can damage it. The lights flash quickly.
- Safe to reset?
- Leave it, call an engineer
- When to call an engineer
- Switch off the DC isolator and call an engineer straight away.
3501Insulation failure
The inverter has measured a leak to earth on the panel side, usually water in a connector or a damaged cable.
- Safe to reset?
- Leave it, call an engineer
- When to call an engineer
- Book an engineer. These faults come and go with the weather and get worse over time.
3701Residual current too high
Current is leaking to earth from the panel side.
- Safe to reset?
- Leave it, call an engineer
- When to call an engineer
- Book an engineer to test the array.
3801–3805DC overcurrent
Too much current from the panels, so feed-in paused briefly.
- Safe to reset?
- Check first
- When to call an engineer
- If it repeats, call us. It can mean strings wired incorrectly.
Inverter and device faults
6002–6412Self-diagnosis: interference device
An internal fault the inverter cannot diagnose itself.
- Safe to reset?
- Leave it, call an engineer
- When to call an engineer
- Note the exact number and call an engineer. It may need SMA service.
6501–6509Overtemperature
The inverter switched off because it got too hot.
- Safe to reset?
- Check first
- When to call an engineer
- Make sure nothing is blocking its vents and it is not in direct sun or a hot, unventilated loft. Call if it repeats.
7500–7501Fan fault
The cooling fan is not working properly.
- Safe to reset?
- Leave it, call an engineer
- When to call an engineer
- Call an engineer before the inverter starts overheating.
7619No data from the energy meter
The inverter is not receiving data from its energy meter, which affects export control and monitoring.
- Safe to reset?
- Check first
- When to call an engineer
- Check the meter has power. If the message stays, call us.
8003Power reduced: temperature
Output has been reduced for more than ten minutes because the inverter is too warm.
- Safe to reset?
- Safe to restart
- When to call an engineer
- If it happens every summer day, the location needs better ventilation.
Written in our own words from the manufacturer’s documentation. For the full list, see SMA manuals and downloads.
SMA questions
What does SMA error 3501 mean?
An insulation failure: the inverter has found a leak to earth on the panel side, usually water in a connector or a damaged cable. It needs an engineer to test the array.
What does an SMA grid fault mean?
The grid at your connection was outside the limits the inverter is allowed to work within, so it disconnected. The inverter is usually fine. Frequent grid faults are worth raising with your DNO first.
Can I reset an SMA inverter myself?
You can switch it off and on at the AC and DC isolators. If the same code returns, leave it off and call an engineer rather than restarting it repeatedly.